Eurotherm’s range of 3200i indicators offer accurate indication of
temperature and process measurements. Process interlocks, including
overtemperature furnace limits, are implemented using relay output
channels.
The emphasis is on ease of use. A simple ‘Quick Start’ code is used to
configure all the functions essential for indication and protecting your
process. This includes input sensor type, measurement range and alarms
making ‘Out the Box’ operation truly achievable. In operation every
parameter has a scrolling text message describing its function and is
available in English, German, French, Spanish or Italian. More advanced
features, including scrolling text messages, are configured using iTools, a PC
based configuration wizard, which is an easy to use and instructive guide to
all the functions available.
Universal input
A wide range of temperature and process inputs can be selected using the
front panel push buttons without the need for any hardware change. This
provides easy on-site set up.
Strain gauge input
Melt pressure and weigh scale inputs can be energised from an internal
10Vdc transducer supply. An automatic shunt calibration routine is
provided to remove zero and span offsets. The display on the 32h8i can
show a full 5 digit value.
Process alarms
Four internal alarm setpoints are provided. They can be used to energise
up to three relay outputs, which can be latched if required. A special
mode, known as ‘Alarm Blocking’, is available which ensures that when the
unit is powered up an alarm must first enter a good state before the alarm
becomes active. This is particularly useful for low alarms which can be
blocked while the process is warming up.
Custom text messaging
Custom messages can be created with iTools and downloaded to the 3200i
to display when an event, alarm or process condition occurs. This provides
the operator with good visibility of what is happening in the process and
provides messages that they can understand and act upon.